BACnet
Last updated
Last updated
©2019 - 2024 Counterbalance Software LLC
Before you begin, you must have an active edge device with a BACnet connector configured. See the Planning for BACnet section.
To configure BACnet:
Login to the Green Stack Console and navigate to Building Engineering
To add BACnet devices:
Select a Site from the system profile tree
Expand Connectivity and select the Building Automation folder
To add devices via BACnet discovery:
Click Add Devices
Select the discovered devices you'd like to add
Click Import Devices to save the devices
To add BACnet points in a managed BACnet device:
Select a BACnet device from the system profile tree
Select the Points tab
To add points via BACnet discovery:
Click Add Points
Select the discovered points you'd like to add
Click Import Points to save the points
Managed BACnet point alarms are automatically annunciated to the Green Stack console by default. The behavior of the alarm and its priority are determined by the configuration of the BACnet point and its associated notification class.
When a new alarm is received, it is prioritized by the assigned notification class priority.
NC Priority | Alarm Priority | Alarm Level |
---|---|---|
0-63 | PRI1 | CRITICAL |
64-127 | PRI2 | WARN |
128-191 | PRI3 | CAUTION |
192-255 | PRI4 | NOTICE |